Target Gas
Electrochemical Sensors (internal) Ammonia (NH3), Carbon monoxide, Chlorine (Cl2), Chlorine dioxide (ClO2), Ethylene (C2H4), Ethylene oxide (C2H4O), Fluorine (F2), Formaldehyde (CH2O), Hydrogen (H2), Hydrogen chloride (HCl), Hydrogen cyanide (HCN), Hydrogen fluoride (HF), Hydrogen sulphide (H2S), Nitric oxide (NO), Nitrogen dioxide (NO2), Oxygen (O2), Ozone (O3), Phosphine (PH3), Silane (SiH4), Sulphur dioxide (SO2), TVOCs (Isobutylene)
Catalytic Sensors (remote) Hydrogen (H2), Methane (CH4), Propane (C3H8)
PID Sensors (remote) TVOCs
Infrared Sensors (remote) Propane (C3H8)
Mechanical
Enclosure ABS / Polycarbonate, corrosion resistant
Copper coated interior to reduce RF interference
IP54 rated with optional splash guard installed
Weight 363 g / 0.80 lbs
Size 127 x 127 x 71 mm / 5.0 x 5.0 x 2.8 inches
User Interface
Display Graphic LCD, yellow border
Magnetic switches to initiate calibration without opening the enclosure
Input/Output
Output BACnet® MS/TP communications
Relay One SPDT dry contact, rated at 30 volts, 2 amps max
Audible Alarm Standard internal buzzer
Electrical
Power Requirement 16-30 VDC, 3 W, Class 2
12-27 VAC, 50-60 Hz, 3 VA, Class 2
Current Draw 55 mA (buzzer & relay energized, 2 sensors)
Wiring 4-conductor, 16 AWG stranded, shielded network wiring (daisy-chain)
Fuses Thermal, resetting
Environmental
Operating Temperature -20°C to 40°C (-4°F to 104°F)
Operating Humidity 15 - 90% RH non-condensing
Certifications
Conforms to CSA-C22.2 No. 205-12 / UL508 (Edition 17):2007
EMC Directive 2004/108/EC, EN 50270:2006, Type 1, EN61010
FCC. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Listed by BTL
RoHS compliant circuit boards
|