Type Single point sampling system using proprietary IR sensor
Gases Refrigerants: CFCs, HFCs, HCFCs, HFOs
Natural Refrigerants: Ammonia, Carbon Dioxide
Measuring Range Refrigerants: 0 to 10,000 ppm
Ammonia: 25 to 10,000 ppm
Carbon Dioxide: 300 to 8,000 ppm
Sensitivity Refrigerants: 1 ppm
Ammonia: 25 ppm
Carbon Dioxide: 10 ppm
Sampling Distance 0 to 500 ft (0 to 150 m)
Display Backlit graphic LCD, three status LEDs
Output 4 to 20 mA
Power Supply 100 to 240 VAC, 50 / 60 Hz
Relays 3 alarm relays, 1 fault relay, SPDT
Rating 3 A @ 250 VAC, resistive load
Ambient Conditions Temperature: 32 to +122 °F (0 to +50 °C)
Humidity: 5 to 90 %RH, non condensing
Altitude: 0 to 6,560 ft (2,000 m)
Enclosure Powder-coated aluminum housing
Size (w x h x d) Approx. 13.7” x 7.7” x 3.6” (350 x 195 x 95 mm)
Weight Approx. 7 lbs. (3.2 kg)
Approvals CE, UL, CSA, EN 61010-1, EN 14624
|